G.R.Y.N Generators

Engineering Design

Databar for the Designer

Output data for 11.5-220KVA

Generator Power KVA STANDBY11.5-1622355068100pp. 115-138.165180-220
Air inlet opening including muting (m2)0.750.751.11.11.12.12.192.192.91
 Air outlet opening including muting (m2)0.90.91.11.11.11.72.12.12.6
 Recommended room size includes mute (length, width) (meters)3.2X5.23.2X5.23.2X5.73.2X5.73.2X6.33.2X6.33.2X6.53.5X6.53.5X6.8

Yield data for 275-1250KVA

Generator Power KVA STANDBY275-330400-500550-600660-715800880100011001250
Air inlet opening including muting (m2)3.85.35.776.86.689.139.139.1312.26
 Air outlet opening including muting (m2)3.34.264.795.455.567.97.97.910.4
 Recommended room size includes mute (length, width) (meters)3.6X7.24.2X7.64.2X8.14.2X8.14.2X8.64.2X8.64.7X9.24.7X9.24.7X9.2

Data for 1400-3300KVA Outputs

Generator Power
KVA STANDBY
14001540165019002100220025002800-3300
Air inlet opening including muting (m2)11.211.213.3515.315.315.78 27.6829.49
 Air outlet opening including muting (m2)9.39.311.412.712.713.1723.0724.58
 Recommended room size includes mute (length, width) (meters)4.7X10.14.7X10.15.2X11.25.2X11.25.2X11.25.2X11.26.3 X 13.36.3 x 14.2

Calculators

kVA to kW conversion calculator
Conversion power 0.8 (cos φ)
Value in kilo-volt ampere kVA
   
Result kW
kW to kVA conversion calculator
Conversion power 0.8 (cos φ)
Value in kilowatt KW
   
Result kVA
kVA to A Conversion Calculator - Three-Phase
Conversion power 0.8 (cos φ)
Value in kilo-volt ampere kVA
   
Result A
A to kVA Conversion Calculator – Three-Phase
Conversion power 0.8 (cos φ)
Value in Ampere A
   
Result kVA