Voltage regulators
AVR-4
The AVR-4 is an electronic device that allows the alternator to produce a constant output voltage. The unit does not include moving parts; so it is able to operate in highly vibrating environments.
The AVR-5 is an electronic device that allows the alternator to produce a constant output voltage. The unit does not include moving parts; so it is able to operate in highly vibrating environments.
AVR-5
AVR-8
The sensor loss protection circuit disables the output when there is no voltage on the sensing input.Analog input is provided to allow external voltage adjustment.AVR has a fixture for a CT droop connection, to allow parallel running with other similarly equipped generators.
The AVR-12 is an electronic device that allows the producer to create a constant output voltage.
The device is equipped with an open-enclosure, resin-cast design and is designed to be installed in the Alternator Termination Box. The unit does not have moving parts; so it is able to operate in highly vibrating environments.
AVR-12
AVR-20
The AVR-20 is an electronic device that allows the manufacturer to produce a constant output voltage.
The device is equipped with an open-enclosure, resin-cast design and is designed to be installed in the Alternator Termination Box. The unit does not have moving parts; so it is able to operate in highly vibrating environments.
The AVR-40 is an electronic device that allows an alternator to produce a constant output voltage.Thanks to its high current output heat diffuser current, it is able to operate in very hot conditions and leads the alternatives that require high excitation currents.The sensing loss protection circuit disables the output when there is no voltage on the sensing input.An analog input ±3V is provided allowing external voltage adjustment. AVR has a facility for a CT droop connection, to allow parallel running with other similarly equipped generators. An overload protection circuit limits the output current to its rated value, preventing the device from malfunctioning under overload or short circuit.
AVR-40
AVR-8-380
AVR-8-380 is an electronic device that allows an alternator to produce a constant output voltage.
The unit measures the voltage of the voltage that varies from phase to phase connection and is able to drive alternators that require high excitation voltages.
The unit does not have a neutral connection and is ideally suited for marine use.
The sensing loss protection circuit disables the output when there is no voltage on the sensing input.
An analog input of ±3V is provided which allows for external voltage adjustment. The AVR has a fixture for a CT droop connection, to allow parallel running with other similarly equipped generators.
An overload protection circuit limits the output current to its rated value, preventing the device from malfunctioning under overload or short circuit.
Input and Detection Voltage
Voltage: Jumper choice 95-132V AC or 190-265V AC
Frequency: 50-60Hz
Exit
Voltage: 90V DC at 200V AC
Current: 4A DC, 8A DC to 15 seconds
Resistance: 15Ohms Minimum
Model 460
Model 440
Input and Detection Voltage
Voltage: Jumper choice 95-132V AC or 190-265V AC
Frequency: 50-60Hz
Exit
Voltage: 90V DC at 200V AC
Current: 4A DC, 8A DC to 15 seconds
Resistance: 15Ohms Minimum
Input and Detection Voltage
Voltage: 85-140V AC
Frequency: 50-60Hz
Exit
Voltage: 90V DC at 110V AC
Current: 10A DC, 15A DC to 15 sec
Model 230
Model 250
Input and Detection Voltage
Voltage: 85-140V AC
Frequency: 50-60Hz
Exit
Voltage: 90V DC at 110V AC
Current: 10A DC, 15A DC to 15 sec
Input voltage
Voltage: 35-150V AC
Frequency: 40-400Hz
Detection Stress
Voltage: 110-220-415V AC
Frequency: 50/60Hz
Exit
Voltage: 90V DC at 110V AC
Current: 10A DC, 15A DC to 15 sec
Model 448
Model 449
Input voltage
Voltage: 35-150V AC
Frequency: 40-400Hz
Detection Stress
Voltage: 110-220-415V AC
Frequency: 50/60Hz
Exit
Voltage: 90V DC at 110V AC
Current: 10A DC, 15A DC to 15 sec
Input voltage
Voltage: 35-150V AC
Frequency: 40-400Hz
Detection Stress
Voltage: 110-220-415V AC
Frequency: 50/60Hz
Exit
Voltage: 90V DC at 110V AC
Current: 10A DC, 15A DC to 15 sec
Model 438
Model 72GP
Input voltage
Voltage: 110-265V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 80-265V AC
Frequency: 50-60Hz
Exit
Voltage: 90V DC at 200V AC
Current: 6A DC, 8A DC to 15 seconds
Resistance 15Ohms Minimum
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 415V AC
Frequency: 50/60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC, 12A DC to 15 sec
Resistance 12Ohms Minimum
Model U6
Model D8, D12, D15, D20
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 415V AC in 2 phases, 220V AC in one phase
Frequency: 50/60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 8A DC 12A to 15 sec – Model D8
Current: 12A DC Forced 20A to 15 Seconds – Model D12
Current: 15A DC Forced 20A to 15 Seconds – Model D15
Current: 20A DC Forced 28A per 15 sec – D20 Model
Resistance 12Ohms Minimum
Input and Detection Voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 5A DC 8A to 15 sec – D5.1
Current: 12A DC 16A to 15 sec – D12.1
Current: 20A DC Forced 25A to 15 Seconds – Model D20.1
Resistance 15Ohms Minimum
Model D5.1, D12.1, D20.1
Model 101
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 415V in 2 phases, 200V in one phase
Frequency: 50/60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 15Ohms Minimum
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 415V in 2 phases, 200V in one phase
Frequency: 50/60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 15Ohms Minimum
Model T10
Model 11P
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Detection Stress
Voltage: 220V/110V
Frequency: 50/60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 15Ohms Minimum
Input and Detection Voltage
Voltage: 415V AC in 3 phases
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 15Ohms Minimum
Model 306
Model 1008
Input voltage
Voltage: 180-250V AC
Voltage Detection
Voltage: 415V AC in 2 phases/220V AC in 3 phases
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 8A DC forced 12A to 15 seconds
Resistance 12Ohms Minimum
Input voltage
Voltage: 180-250V AC
Voltage Detection
Voltage: 415V AC in 2 phases/220V AC in 3 phases
Frequency: 50-60Hz
Exit
Voltage: 180V DC at 220V AC
Current: 8A DC forced 12A to 15 seconds
Resistance 12Ohms Minimum
Model 1808
Model 2000
Input voltage
Voltage: 180-250V AC
Voltage Detection
Voltage: 415V in 2 phases/220V in one phase
Frequency: 50-60Hz
Exit
Voltage: 180V DC at 220V AC
Current: 8A DC forced 12A to 15 seconds
Resistance 12Ohms Minimum
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Voltage Detection
Voltage: 110-220-415V AC
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 12A to 15 seconds
Resistance 12Ohms Minimum
Reference: 3007PIN
Model 206 and 208
Input voltage and detection
Voltage: 415V
Frequency: 50-60Hz
Exit
Voltage: 200V DC at 220V AC
Current: 6A DC 10A to 15 sec – Model 206
Current: 8A DC 12A to 15 sec – Model 208
Resistance 12Ohms Minimum
Input voltage
Voltage: 220V AC
Frequency: 50-60Hz
Voltage Detection
Voltage: 110-220-415V
Frequency: 50-60Hz
Exit
Voltage: 200V DC at 220V AC
Current: 10A DC forced 15A to 15 seconds
Resistance 12Ohms Minimum
Reference: IG10BL
Model 63-7
Input voltage
Voltage: 180-250V AC
Frequency: 50-60Hz
Voltage Detection
Voltage: 220V AC
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 4A DC 8A for 15 seconds – Model 63-4
Current: 7A DC 12A for 15 seconds – Model 63-7
Resistance 12Ohms Minimum
Input voltage and detection
Voltage: 415V
Frequency: 50-60Hz
Exit
Voltage: 100V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 18Ohms Minimum
Model 43
Model 200
Input voltage and detection
Voltage: 415V
Frequency: 50-60Hz
Exit
Voltage: 200V DC at 220V AC
Current: 6A DC forced 10A to 15 seconds
Resistance 18Ohms Minimum
Input voltage and detection
Voltage: 415V
Frequency: 50-60Hz
Exit
Voltage: 265V DC
Current: 10A DC 18A to 15 sec – Model 2510
Current: 15A DC Forced 22A per 15 Seconds – Model 2515
Resistance 15Ohms Minimum
Model 2510 and 2515
Model 3810 and 3815
Input voltage and detection
Voltage: 415V in 2 phases
Frequency: 50-60Hz
Exit
Voltage: 380V DC
Current: 10A DC 18A to 15 sec – Model 3810
Current: 15A DC Forced 22A per 15 sec – Model 3815
Resistance 15Ohms Minimum